Intermediate relay MRP-2M 13mm of ultranarrow case for DIN-rail

Промежуточное реле МРП-2М
MRP-2M AC230V UHL4
750.00 руб. с НДС

MRP-2M AC230V UHL2
1035.00 руб. с НДС

MRP-2M ACDC12V UHL4
750.00 руб. с НДС

MRP-2M ACDC12V UHL2
1035.00 руб. с НДС

MRP-2M ACDC24V UHL4
750.00 руб. с НДС

MRP-2M ACDC24V UHL2
1035.00 руб. с НДС

 
  • Are applied to amplification, galvanic decoupling and increasing the amount of contacts of used equipment
  • Indication of output status
  • Built-in protection of switching element against inductive emissions arising from the opening of the relay
  • Width of the case is 13mm
 
PURPOSE OF THE RELAY
 Intermediate relays (auxiliary) type of MRP-2M are designed for galvanic isolation between power circuits and circuits of control of remote activation load by applying a control voltage to the input of the relay, as well as for use as an intermediate relay.
 
DESIGN OF THE RELAY
 Relay is produced in a plastic case with a unified front connection wires power and switched circuits. Mounting is carried out on a DIN rail  width 35mm (GOST R IEC 60715-2003) or on a smooth surface. To set on a smooth surface, you need to push locks. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel there is yellow indicator os status contact group and circuit connection.
 
OPERATION OF THE RELAY
 Switching the relay is carried out by a supplying control voltage to the power contacts, with switch-on indicator lights on the front panel.
 
SPECIFICATION OF THE RELAY  MRP-2M
A parameter
Unit
MRP-2M ACDC12V
MRP-2M ACDC24V
MRP-2M AC230V
Supply voltage
V
ACDC12
ACDC24
AC230
Power consumption of the coil, not more
W
0,5W/4VA
1,0VA
0,5W/4VA
Time in switched on state
 
not limited
Time relay switching on, not more
ms
25
Time relay switching off, not more
ms
50
Quantity and type of contacts
 
2 switching groups
Maximum switching voltage
V
250
Maximum switching current: AC250V 50Hz (AC1)/DC30V (DC1)
A
5
Maximum switching power: АС250V 50Hz (АС1)/DC30V (DC1)
VA/W
1250/150
Electrical strength (supply - contacts)
V
АС2000 (50Hz - 1min)
Mechanical endurance, not less
cycles
10х106
Electrical endurance, not less
cycles
100000
Maximum operating rate, not more
cycle/h
600
Operating temperature range (different versions)
0C
-25…+55 (UHL)
-40…+55 (UHL2)
Storage temperature
0C
-40...+70
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)
 
level 3 (2kV A1-A2)
Climatic modification and placement category by GOST 15150-69 (non-condensing)
 
UHL4 or UHL2
The degree's protection at case/terminals according to by GOST 14254-96
 
IP40/IP20
The degree of pollution in accordance with GOST 9920-89
 
2
Relative humidity of air
%
up to 80 (at 250C)
Operating position in space
 
artbitrary
Mode
 
round the clock
Dimensions
mm
13х93х62
Weight
kg
0,065
 
CIRCUIT CONNECTION
Схема подключения МРП-2М
 
DIMENSIONS OF THE RELAY
Габариты 13*93*62
 
Title
Order code
File to download
(manual)
File date
MRP-2M AC230V UHL4
4640016936946
v03.07.2015
MRP-2M AC230V UHL2
4640016936953
MRP-2M ACDC12V UHL4
4640016937790
MRP-2M ACDC12V UHL2
4640016937806
MRP-2M ACDC24V UHL4
4640016936960
MRP-2M ACDC24V UHL2
4640016936977
 