Single-phase power limiter ОМ-63 (63A, 14 kW)

Ограничитель мощности ОМ-63
OM-63 АС230V UHL4
1990.00 руб. с НДС

OM-63 АС230V UHL2
2190.00 руб. с НДС

 
  • Rated load current is 63A (14kW)
  • Synchronous control of the relay - closure relay contacts is carried out by passing mains voltage through a zero
  • Setting the time switch-on after the excess power from the 10s up to 360s
  • Two-threshold protection from overvoltage and undervoltage
  • Built-in varistor protection from pulse spikes mains voltage
  • Keeps working capacity at a supply voltage up to 400V
  • Possibility of manual control
 
PURPOSE OF THE DEVICE
 Power limiter OM-63 provides the control value of the maximum power in single-phase nets and switches off the supply of electricity from the consumer in case of excess power consumption than the set value, and also protects the equipment connected to it (in the flat, office and so on.) from the damaging action of pulsed power surges caused by electromagnetic pulses of close lightning strikes or actuation closely spaced and connected to the same net of electric motors, magnetic starters or electromagnets, and also switches off equipment, when mains voltage is leaving an allowable ranges (<160V or> 265V), thereby preventing equipment damage and possible fire, followed by a fire. Can be used in any net configuration: TN-C, TN-S, TN-C-S, TT.
 
 WARNING: OM-63 does not replace other protection devices (automatic circuit breakers, surge arresters, RCDs, etc.).
 
DESIGN OF THE DEVICE
 Device is mounting on a DIN rail width 35mm (GOST R IEC 60715-2003) with a unified front connection wires power and switched circuits. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel there are: two-color LED (green/red) "NORMAL/OVERLOAD power", red LED "ALARM voltage", yellow LED - switching on the contact of relay, button "TEST" - manual control, a switch of time delay on "ton". On the right side of the case there is a switch of setting level of power limit "P, kW (Current, A). After setting required power level limit the authorized representative of power sales organizations must remove the knob and covering the hole with a filling disposable nameplates (supplied in kit), beforehand making it all the necessary data.
 
OPERATION OF THE DEVICE
 When the supply voltage is turned on, OM-63 controlls the value of voltage and the value of consumed by the load current, calculates the acting value of the power consumption. If the power consumption does not exceed the set valuelights up green indicator "NORMAL". With long-term increase in the power consumption more than the set value, the OM-63 disconnects the load at the time set by the user. During a counting of this time lights the red LED  "OVERLOAD power». Time OFF at overload is fixed. Restart time is set by the consumer by switch on the front panel.
 After turns off a load starts the set by switch counting of time "ton". During counting of this time flashes the green LED. On expiry this time, the load is connected, if the power of the exceeding tendency kept, then begins time off - 15s. After five cycles of turn on and off the load, the set time on switch is increased to 360s, which eliminates some of the load connection.
 Auxiliary mode - voltage control. When the supply voltage, device can stand ready time 5s while the indication is not working. If the voltage is in appropriate ranges the green LED start to flash pointing to the counting delay time on 10s, then the load is connected to the net of supply voltage and lights up a green indicator "NORMAL" and yellow indicator of load connection.  If the supply voltage reaches the upper off threshold (265V), the device disconnects the load through the 0,1s and the red LED "ALARM voltage" turns on, if the supply voltage reaches the lower off threshold (160V), the device disconnects the load through 10s, during the counting time is flashing red LED "ALARM voltage". After switching off the load the yellow LED turns off, red LED "ALARM voltage" sometimes goes out indicating at a low voltage power supply net. When restoring the supplying net, device connects load through the 10s, during the counting time flashes the green indicator. When appears in a net powerful pulses of voltage built-in varistor shunts them to the value of safe equipment. The user can by himself connect and disconnect the load manually by pressing the "TEST" button. When disconnecting the load by button "TEST" indicators "NORMAL" and "ALARM voltage" alternately are flashing red and green colors appropriate. The device remains switched off as well after removal and supply voltage. Turn on a load can only by re-pressing the "TEST" button.
 
WARNING: Do not use the manual mode for emergency net status. When you try to manually activate the emergency mode, the device does not allow to apply power to the load. At connecting a device should be considered cross-section of current-carrying wires.
 
Recommended conductor cross-section
Power (kW)
1,0
1,5
2,0
3,0
4,0
5,0
6,0
8,0
10,0
14,5
Current (A) (Usupply 230V)
4,3
6,5
8,7
13,0
17,4
21,7
26,0
35,0
43,5
63,0
Cross-section mm2(Cu)
1,0
1,0
1,0
1,0
2,5
4,0
6,0
10,0
10,0
16,0
Cross-section mm2 (Al)
2,5
2,5
2,5
2,5
4,0
6,0
10,0
16,0
16,0
25,0
 
SPECIFICATION OF THE POWER LIMITER OM-63
Parameters to limit the power
Thresholds load disconnection in excess power/at current
(Usupply=230V)
kW/A
(1,0/4,3), (1,5/6,5), (2,0/8,7), (3,0/13,0), (4,0/17,4), (5,0/21,7), (6,0/26), (8,0/35,0), (10,0/43,5), (14,5/63,0)
Fixed delay disconnection in excess power, toff
s
15
Delay ON, ton
s
10, 20, 30, 60, 90, 120, 180, 240, 300, 360
Parameters of voltage protection
Delay ON (restart delay)
s
10
The upper threshold of load disconnection/actuation delay
Uup/s
265/0,2
The upper threshold of rapid disconnection load/actuation delay
Uup/s
300/0,02
The lower threshold of load disconnection/actuation delay
Ulow/s
160/10
The lower threshold of rapid disconnection load/actuation delay
Ulow/s
130/0,1
Hysteresis upper and lower thresholds (return)
%
3
Protection parameters against pulse noises
Level of voltage limit at noise's current 100A, not more
kW
1,2
The maximum absorption energy (single pulse of 10/1000 microseconds)
Joule
40
The maximum absorption current (single pulse of 8/20 microseconds)
A
1200
The maximum absorption current (repetitive pulses of 8/20 microseconds)
A
600
Time of actuation of pulse protection
ms
<25
Supply
Rated voltage supply
V
230
Frequency of voltage supply
Hz
50
Maximum voltage supply
V
400
Switching capacity of contacts
Rated current of load
A
63
Rated power of load
kW
13,8
Maximum current of load, (active – АС1, 30min)
A
80
Maximum power of load (active – АС1, 30min)
kW
17,6
Maximum an overlooked short-circuit current (not more 10ms)
A
4500
Technical data
Deviation of measurement, not more
%
6
Dimensions
mm
83x35x67
Weight
kg
0,160
The degree's protection at case/terminals according to by GOST 14254-96
 
IP40/IP0
Operating temperature range (different versions)
0C
-25...+55 (UHL4)
-40...+55(UHL2)
Storage temperature
0C
-50...+70
Warranty period of operation
months
24
Service life, not less
years
10
 
CIRCUIT CONNECTION
Схема подключения ОМ-63
 
DIMENSIONS OF THE DEVICE
Габариты 35*83*62 ОМ-63
 
 
Title
Order code
File to download
(manual)
File date
OM-63 АС230V UHL4
4640016930500
v05.07.2015
OM-63 АС230V UHL2
4640016930517
 
English