PURPOSE OF THE RELAY
 Pulse relay of light RIO-2 is designed to remotely control lighting in the hallway, on the stairs, floor, etc. via the parallel connection of buttons with backlight. Additional control inputs allow you to centrally switch on or off light in the whole house, depending on the adjusted mode organize different lighting control circuit. Using the block diodes MD-3 allows to create multi-level lighting control circuit.
 
DESIGN OF THE RELAY
 Relay is produced in a plastic case with a unified front connection wires power and switched circuits. Mounting is carried out on a DIN rail  width 35mm (GOST R IEC 60715-2003) or on a smooth surface. To set on a smooth surface, spring locks must be changed in recent holes, fixing a spring lock, which are located on the back side of the case. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel is switch of modes and setting time off lighting for mode automatic timer, an indicator of the availability of mains voltage "U" and starus indicator of contacts executive relay "K"
 
OPERATION OF THE RELAY
 The relay does not require auxiliary power. Power is supplied from the lighting network. A feature of the relay is to use a technology of switching contacts - «zero sync», which ensures a high load capacity of the contact group. Closing and opening of the contacts is performed at the moment when the mains voltage through a "0", which provides a limit inrush current at the time of closing or opening contacts. The relay has three control inputs, that having different appointments, depending on the selected operating mode. The motion sensor is connected to terminal Y1.
 Mode 1 - mode of pulse relay. When a control command is filed to the input «Y1» (On) contacts A1-14 closes. When a control command is filed to the input «Y2» (Off) contacts A1-14 opens. When a control command is filed to the input «Y» (On/Off) a status contact A1-14 reversed. Indicator «U» - the availability of the line voltage. The indicator "K" shows the status of the relay contacts, the indicator is on - contacts are closed. Working in pulse relay allows control of lighting groups via two wires in building lighting systems for one or more groups of lighting fixtures. Can operate with a motion sensor (switch on by the sensor, turn off by the button or time *)
 Mode 2 - mode of 3 cross switches. Control of executive relay is performed for each input imitation the work of three switches with fixed position of contacts in the "On" or "Off" status. Mode of cross-switches lets you to control the lighting in any of the three switches, that located in different places rooms, in independence of the position at which the each switch is.
 Mode 3 - mode of automatic timer. Mode is designed to automatically turn off the lighting on the counting time seting by the user. Disconnect automatically after an end of time delay. If the control signal is supplied to the switch, the time is reset and the cycle is repeated until the delay expires. Relay operation mode is selected by switch position indicator on the front panel.
 
* - function is available in relay of the release at 12.2015 year.
 
 WARNING: A position of contacts for supply can be arbitrary, starting at the first operation (OFF) state of the contact is restored.
 
SPECIFICATION OF THE RELAY RIO-2
A parameter
Unit
RIO-2 AC230V
RIO-2 ACDC24V
Supply voltage
V
АС160-250
ACDC24±10%
Minimum time feed control signal, not less
s
0,3

Quantity button switches with indicator glow discharge with a current of 1mA at input "Y", not more

pcs
20

Quantity button switches with indicator glow discharge with a current of 1mA at input "Y1", "Y2",  not more

pcs
5
The delay time for the automatic switch off mode, toff min 0,5, 1, 1,5, 2, 3, 5, 10, 20
Delay relay, not more
s
0,25
Nominal/maximum switching voltage
V
250/440
Maximum switching current: AC250V 50Hz (AC1)/DC30V (DC1)
A
16
Maximum switching current (<4s at pulse duty factor 10)
A
30
Maximum load incandescent lamps
W
2000

Maximum load fluorescent lamps (uncompensated) cosφ = 0.5

pcs
25х36W/13х65W
Maximum switching power: АС250V 50Hz (АС1)/DC30V (DC1)
VA/W
4000/480
Minimum switching power (100V/5mA)
mW
500
Mechanical endurance, not less
cycles
10х106
Electrical endurance, not less
cycles
100000
Electrical strength (supply - contact) (50Hz - 1min)
V
АС2000
Maximum operating rate, not more
operations/h
600
Quantity and type of contacts
 
1 close
Operating temperature range
0C
-25…+55
Storage temperature
0C
-40...+70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)   level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)   level 3 (2kV A1-A2)
Climatic modification and placement category by GOST 15150-69 (non-condensing)
  UHL4
The degree's protection at case/terminals according to by GOST 14254-96
  IP40/IP20
The degree of pollution in accordance with GOST 9920-89
  2
Relative humidity of air
%
up to 80 (at 250С)
Operating position in space
 
artbitrary
Mode
 
round the clock
Dimensions
mm
18х93х62
Weight
kg
0,08
 
DIAGRAMS OF OPERATING THE RELAY
Диаграмма работы РИО-2
 When a control command is filed to the input «Y1» (On) contacts A1-14 closes. When a control command is filed to the input «Y2» (Off) contacts A1-14 opens. When a control command is filed to the input «Y» (On/Off) status of contacts A1-14 is reversed. Indicator «U» - the availability of a linear voltage. The indicator "K" - shows the status of the relay contacts, the indicator is on - contacts are closed. Work in pulse relay mode allows you to control lighting in groups of two wires at building lighting systems for one or more groups of of lighting fixtures.
Диаграмма работы РИО-2 (2)
 Control of executive relay is performed for each input imitation work of three switches with fixed position of  contacts in the "On" or "Off" status. Mode of cross-switches lets you control the lighting in any of the three
switches located in different places rooms, in independence at position in which the each switch.
Диаграмма работы РИО-2 (3)
 Mode is designed to automatically turn off the lighting on the counting time setting by the user. Disconnect is
automatically after the end of a preset time delay. If the control signal is supplied to the switch, the time is
reset and the cycle is repeated until the delay expires. Mode of relay is selected by switch position of pointer
at the front panel.
 
CIRCUITS CONNECTION
Схема подключения РИО-2          Схема подключения РИО-2 с фотодатчиком
 
Схема подключения РИО-2 (2)
Local and central control of several pulse relays
 Each pulse relay is controlled by buttons (local control); each level or set of impulse relays is controlled at the same time from a point (central control) from an appropriate place (central control).
 
Схема подключения РИО-2 (3)
Local, central, central multi-level control
 Each pulse relay is controlled by buttons (local control); each level or set of pulse relays is controlled at the same time from an appropriate place (central control); all levels at the same time are controlled from a command from one place (central multi-level control).
 
DIMENSIONS OF THE RELAY