Relay of temperature control TR-15 (a thermistor relay)

TR-15 ACDC24V/АС230V UHL4 with TD-2
1900.00 руб. с НДС

TR-15 ACDC24V/АС230V TM with TD-2
2622.00 руб. с НДС

TR-15 DC12V UHL4 with TD-2
2622.00 руб. с НДС

TR-15 DC12V UHL2 with TD-2
2622.00 руб. с НДС

 
  • Precision discrete temperature setting (through 10C)
  • Wide range of controlled temperatures –55 ...+1250C
  • Ability to work in mode "heating" or "cooling"
  • Output contact - 1 switching group 16A/250V
  • Control of sensor serviceability
  • Switching hysteresis 0,5 or 20С
  • It works with digital temperature sensors DS18B20 Dallas Semiconductor (Maxim)
 
PURPOSE OF THE RELAY
 Temperature relay TR-15 is designed to control and maintain the preset temperature mode at the temperature sensor signals, generated on the basis of the chip DS18B20 Dallas Semiconductor (Maxim) in the premises, vegetable storage, water heating systems, cooling systems, liquids, objects, and so on, and also for use as components in the automation devices. Temperature relay is supplied with sensors TD-2 (specify when ordering).
 
DESIGN OF THE RELAY
 Relay is produced in a plastic case with a unified front connection wires power and switched circuits. Mounting is carried out on a DIN rail  width 35mm (GOST R IEC 60715-2003) or on a smooth surface. To set on a smooth surface, you need to push locks. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel there are: DIP-switch for setting the hysteresis zone «Δ0,5/Δ2», to select the "00C\+100", to set a positive or negative temperature "+t0C/-t0C", to select mode cooling/heating, rotary switch "TENS" to set the tens of temperature, rotary switch "UNITS" to set the temperature unit, the red LED "+t0C" of heating, blue LED "-t0C" of cooling, yellow LED of actuation built-in executive relay "" .
 
OPERATION OF THE RELAY
 Termorele can work in two modes: "heating" or "cooling".
 "Heating" - a mode in which the executive relay is turned on, if the controlled temperature is below the set (heater).
 "Cooling" - a mode in which the executive relay is turned on, if the controlled temperature exceeds the set limit (fridge). The operating mode is selected by the switch "cooling/heating".
 Enabling of the executive relay is controlled by a yellow indicator "". When the relay is turned on, the yellow LED lights up and the contacts 11-14 are closed. In "heating" mode when power is turned on, if the temperature in the controlled point will be below set, the relay will turn on. Upon reaching the set temperature (t0Cset) - the relay will switch off. When cooling, the re-activation of the relay will take place at t0Cset - Δ. In the "cooling" mode at power up, if the temperature in the controlled point will be above the set, the relay will turn on. Upon reaching the set temperature a relay turns off. At the next time of the temperature increases, the relay will turn on at temperature t0Cset+ Δ.
 
 WARNING: If using more that 3500W power devices is recommended to use intermediate relays or contactors, the appropriate load.
 
Indication of modes
Status of indicators Functional purpose
Blue enabled t0Cset in range -55...00C
Red enabled t0Cset  in range -0...+990C
Red enabled and flashes t0Cset in range +100...+1250C
Alternation blue and red enabled
1. Wrong temperature setting t0Cset (above +1250C or below -550C)
2. Broken sensor, its malfunction or incorrect connection
Yellow enabled Executive relay enabled

 

SPECIFICATION OF THE RELAY OF TEMPERATURE CONTROL TR-15
A parameter Unit TR-15
Rated supply voltage
V ACDC24/AC230 DC12
Power consumption, max
VA
2
Range of controlled temperature
0С
-55...+125
Deviation of temperature measurement: from –10 to 850С
                                                                      in the rest of the operating range
0C
±0,5 
± 2
Temperature hysteresis
0C
0,5or 2
Availability time, not more
s
2,5
Maximum switching voltage
V
400 (AC1/5A)

Maximum switching current: AC250V 50Hz (AC1)/DC30V (DC1)

A
16
Maximum switching power: АС250V 50Hz (АС1)/DC30V (DC1)
VA/W
4000/480
The maximum voltage between the power supply circuits and relay contacts
V
АС2000 (50Hz - 1min)
Mechanical endurance, not less
cycles
10х106
Electrical endurance, not less
cycles
100000
Quantity and type of contacts
 
1 switching group
The degree's protection at case/terminals according to by GOST 14254-96
 
IP40/IP20/IP68
Operating temperature range (different versions)

0C

-25…+55 (UHL4)
-40…+55 (UHL2)
Storage temperature

0C

-40....+70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)   level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)   level 3 (2kV A1-A2)
The degree's protection at case/terminals according to by GOST 14254-96
  UHL4 or UHL2
The degree of pollution in accordance with GOST 9920-89
  2
Relative humidity of air
%
up to 80 (at 250C)
Operating position in space
 
artbitrary
Mode
 
round the clock
Dimensions
mm
18х93х62
Weight
kg
0,075
* Supplied with sensor TD-2. The standart cable length of temperature sensor TD-2 (-55…+1250С) is 2 meters.
 
Sensor type TD-2 (bill of lading)
-55…+1250C
Dielectric strength between the sensor case and conclusions
АС1000V (1min)
Isolation resistance, not less
100megohm (at АС500V)
 
DIAGRAMS OF OPERATING THE RELAY
Диаграмма работы ТР-15 (1)    Диаграмма работы ТР-15 (2)
 
CIRCUITS CONNECTION
Схема подключения ТР-15 (1) Схема подключения ТР-15 (2)

 Products with the performance ACDC24V/AC230V voltage power ACDC24V is supplied to terminals "+A3", "A2". When powered with DC voltage "+Usupply" is connected to the terminal "+ A3". Voltage supply AC230V is fed to terminals "A1", "A2".

 Products with the performance DC12V voltage power is supplied to terminals "+А1", "А2". When powered with DC voltage "+Usupply" is connected to terminal "+А1".

 
DIMENSIONS OF THE RELAY
Габаритные размеры реле в корпусе 18*93*62мм
 
DIMENSIONS OF THE SENSOR
Габариты ТД-2
 
Title
Order code
File to download
(manual)
File date
TR-15 ACDC24V/АС230V UHL4 with TD-2 4640016935086 Download v09.11.2015
TR-15 ACDC24V/АС230V TM with TD-2 4640016935024
TR-15 DC12V UHL4 4640016936175
TR-15 DC12V UHL2 4640016936168

 

English