Relay of temperature control TR-30 (a thermistor block), load up to 30A!

Реле контроля температуры ТР-30
TR-30 АС230V UHL4
1800.00 руб. с НДС

TR-30 АС230V UHL2
1980.00 руб. с НДС

TR-30 DС12V UHL2
1980.00 руб. с НДС

Dimensions of temperature sensors   Download (sensors ordered separately if necessary)
 
  • Dustproof waterproof execution
  • Precision discrete temperature setting (through 10C)
  • Wide range of controlled temperatures –55 ...+1250C
  • Ability to work in mode "heating" or "cooling"
  • Output closure contact -30A/250V (7,5kW)
  • Control of sensor serviceability
  • Adjustable switching hysteresis 0,5 or 20С
  • It works with digital temperature sensors DS18B20 Dallas Semiconductor (Maxim)
 
PURPOSE OF THE RELAY
 Temperature relay TR-15 is designed to control and maintain the preset temperature mode at the temperature sensor signals, generated on the basis of the chip DS18B20 Dallas Semiconductor (Maxim) in the premises, vegetable storage, water heating systems, cooling systems, liquids, objects, and so on, and also for use as components in the automation devices.
 
DESIGN OF THE RELAY
 The relay is produced in a hermetic a plastic case. The lower part of the case there are pressure seals for cables of power supply and switched circuit. Mounting is carried out on a smooth surface. To install the relay, you must remove the transparent front cover, through the holes located at the corners of the case, fix the sleeve with four screws M4. Terminal design of supply provides robust clamp wires up to 1,5mm2. Terminal design of switched circuit provides robust clamp wires up to 3,31mm2. On the board of device there are: two rotary switches for setting temperature "t0С" (setting values units 0-9 and tens 0-9), switch "+t/∆" for setting a positive or negative temperature, husteresis zone and mode of operation  (cooling - heating), red LED "+t"  of heating mode, blue LED "-t"  of cooling mode, yellow LED of enabled executive relay.
 
 WARNING: It is forbidden to carry out any work with the relay under voltage.
 
OPERATION OF THE RELAY
 Termorelay can work in two modes: "heating" or "cooling".
 "Heating" - a mode in which the executive relay is turned on, if the controlled temperature is below the set (heater).
 "Cooling" - a mode in which the executive relay is turned on, if the controlled temperature exceeds the set limit (fridge).
 The operating mode is selected by switch "+t/Δ", first five switch positions corresponds to the cooling mode "Cooling", the following five positions of  switch heating mode "Heating". Enabling of the executive relay is controlled by a yellow indicator. When the relay is turned on, the yellow LED lights up and the contacts are closed. In "heating" mode when power is turned on, if the temperature in the controlled point will be below set, the relay will turn on. Upon reaching the set temperature (t0Cset) - the relay will switch off. When cooling, the re-activation of the relay will take place at t0Cset - Δ (taking into account the hycteresis). In the "cooling" mode at power up, if the temperature in the controlled point will be above the set, the relay will turn on. Upon reaching the set temperature a relay turns off. At the next time of the temperature increases, the relay will turn on at temperature t0Cset+ Δ (taking into account the hysteresis).

 Setting the range of temperature and hysteresis by switch «+t/∆»:
  • «100+t/2» - range from +1250С to +1000С hysteresis 20С
  • «+t/2» - range from +990С to +00С hysteresis 20С
  • «+t/0.5» - range from +990С to +00С hysteresis 0,50С
  • «-t/2» - range from –550С to -00С hysteresis 20С
  • «-t/0.5» - range from –550С to - 00С hysteresis 0,50С
 Control of operating modes is carried out on indicators.
 
 WARNING:  If using more that 7500W power devices is recommended to use intermediate relays or contactors, the appropriate load.
Indication of modes
Status of indicators
Functional purpose
Blue enabled
t0Cset in range -55...00C
Red enabled
t0Cset  in range -0...+990C
Red enabled and flashes
t0Cset in range +100...+1250C
Alternation blue and red enabled
Wrong temperature setting t0Cset (above +1250C or below -550C)
Simultaneous flashing blue and red
Broken sensor, its malfunction or incorrect connection
Yellow enabled
Executive relay enabled
 
SPECIFICATION OF THE RELAY OF TEMPERATURE CONTROL TR-30
A parameter
Unit
TR-30 AC230V
Rated supply voltage
V
АС230 ± 10%
Power consumption, max
VA
2
Range of controlled temperature
°C
-55...+125
Deviation of temperature measurement: from –10 to 850С
                                                                      in the rest of the operating range
0C
±0,5
±2
Temperature hysteresis
0C
0,5 or 2
Availability time, not more
s
2,5
Maximum switching voltage
V
400
Maximum switching current: AC250V 50Hz (AC1)/DC30V (DC1)
A
30
Maximum switching power: АС250V 50Hz (АС1)/DC30V (DC1)
VA/W
7500/900
The maximum voltage between the power supply circuits and relay contacts
V
АС2000 (50Hz - 1min)
Mechanical endurance, not less
cycles
10х106
Electrical endurance, not less
cycles
100000
Quantity and type of contacts
 
1 normally open contact
The degree's protection at case/terminals according to by GOST 14254-96
 
IP54
Operating temperature range (different versions)
0C
-25…+55 (UHL4)
-40…+55 (UHL2)
Storage temperature 0С -40...+70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)
  level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)
  level 3 (2kV A1-A2)
The degree's protection at case/terminals according to by GOST 14254-96 (non-condencing)
  UHL4 or UHL2
The degree of pollution in accordance with GOST 9920-89
 
2
Relative humidity of air
%
up to 80 (till 250C)
Operating position in space
 
artbitrary
Mode
 
round the clock
Dimensions
mm
82х80х56
Weight
kg
0,215
 
DIAGRAMS OF OPERATING THE RELAY
Диаграмма работы ТР-30 (1)    Диаграмма работы ТР-30 (2)
 
CIRCUIT CONNECTION
Схема подключения ТР-30
 
DIMENSIONS OF THE RELAY
Габариты 82*80*56
 
DIMENSIONS OF THE SENSOR
Габариты ТД-2
ORDERED SEPARATELY
 
Title
Order code
File to download
(manual)
File date
TR-30 АС230V UHL4
4640016935123
v10.08.2015
TR-30 АС230В UHL2
4640016935116

 

English