  • Control of three-phase four-wire voltage net with neutral
  • Overvoltage control at any phase from 240V to 295V (switch, 10 positions)
  • Undervoltage control at any phase from 165V to 220V (switch, 10 positions)
  • Control of alternation phases
  • Control of break phases
  • Control of "stiking" phases
  • Operation delay from 0,1 to 10s
 
PURPOSE OF THE RELAY
 Relay control voltage RKN-3-15-15 is designed to control the availability, "sticking" and order of alternation of phases in three-phase circuits of voltage in net with neutral, and for the control of undervoltage and overvoltage above and below the set threshold.
 
DESIGN OF THE RELAY
 Relay is produced in a plastic case with a unified front connection wires power and switched circuits. Mounting is carried out on a DIN rail  width 35mm (GOST R IEC 60715-2003) or on a smooth surface. To set on a smooth surface, you need to push locks. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel there are two switches to set upper "Uphase>" and lower "Uphase<" thresholds, regulator of actuation time "t", two red indicators of net error "U>", "U<",  yellow indicator of built-in executive relay "", three red indicators of availability phases "L1", "L2", "L3".
 
OPERATION OF THE RELAY
 The relay is powered by controlled net. For this you need to connect three controlled phases to terminals L1, L2, L3, neutral wire to terminal N.
 
 WARNING: A connection the neutral wire to terminal N is must!
 
 Upper "Uphase>" and lower "Uphase<" thresholds are setting by using potentiometers, that located on the front panel. A delay of actuation relay is exhibited by medium potentiometer. When power is applied, if a delay is setted and all controlled parameters are normal, the relay will turn on at the end of the counting delay time t, and relay contacts 11-12, 21-22 will be open and contacts 11-14, 21-24 will be close. A flashing indicator "" signals about the counting time delay actuation at which the end of it the buil-in relay switches. At a deviation of one of the parameters of the nominal value, turn on the indication of error and relay switches off after the end of delay. Upon returning the controlled parameter to normal, the indication of error is switched off immediately, and the relay switches after the end of actuation delay. At loss of all three phases a relay turns off without counting delay of actuation time set the user.
 
 WARNING: In violation an order of alternation phases the is a brief alternating turning on indicators «U>», «U<».
 
 Status of indicators «L1», «L2», «L3»:
  • In case of availability of all phases all three indicators turns on
  • In the absence of any phase will turn off  the appropriate indicator «L1», «L2», «L3».
  • When the neutral wire breaks, indicators «L1», «L2», «L3» have little noticeable glow and indicators «U>», «U<», «» is turned off.
  • When you connect the neutral wire to one of the terminals «L» for connection of phase, and phase to terminal «N», turns off the appropriate indicator «L1», «L2», «L3», indicators «U>», «U <» will be turned on.

 

SPECIFICATION OF THE RELAY RKN-3-15-15
A parameter
Unit
RKN-3-15-15
Phase supply voltage Urated, 50Hz
V
58/100
127/220
230/400
Allowable voltages Uphase max /Uphase min
V
86/39
188/85
330/130
Overvoltage thresholds «Uphase
V
61, 64, 67, 68, 69, 70, 71, 72, 73, 74, 76, 78
132, 137, 142, 145, 148, 151, 154, 157, 160, 163
240, 260, 265, 270, 275, 280, 285, 290, 295
Undervoltage thresholds «Uphase
V
42, 43, 44, 45, 46, 47, 48, 49, 52, 55
91, 94, 97, 100, 103, 106, 109, 112, 117, 122
165, 170, 175, 180, 185, 190, 195, 200, 210, 220
Deviation of operation threshold
%
Urated ±1,5
The width of zone of the "hysteresis" operation threshold
%
Urated ± 2,5
Adjustable delay of actuation
s
0,1-10
The power consumed by the net, not more
VA
4
Maximum switching current: AC250V 50Hz (AC1)/DC30V (DC1)
A
8
Maximum switching voltage
V
400 (AC1/2A)
Maximum switching power: АС250V 50Hz (АС1)/DC30V (DC1)
VA
2000/240
The maximum voltage between the power supply circuits and relay contacts
V АС2000 (50Hz - 1min)
Mechanical endurance, not less
cycles
10х106
Electrical endurance, not less
cycles
100000
Quantity and type of contacts   2 switching groups
Operating temperature range (different versions)
0C
-25…+55 (UHL4)
-40…+55 (UHL2)
Storage temperature
0C
-40…+70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)   level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)   level 3 (2kV A1-A2)
Climatic modification and placement category by GOST 15150-69 (non-condensing)
  UHL4 or UHL2
The degree's protection at case/terminals according to by GOST 14254-96
  IP40/IP20
The degree of pollution in accordance with GOST 9920-89
  2
Relative humidity of air
%
up to 80 (at 250C)
Height above sea level
m
till 2000
Operating position in space
 
artbitrary
Mode
 
round the clock
Dimensions
mm
18х93х62
Weight
kg
0,081
 
DIAGRAM OF OPERATING THE RELAY
Диаграмма работы РКН-3-15-15
 
Deviation of controlled parameter
Indicators
Uphase>
Uphase<
Overvoltage «U>»
Yes
-
Undervoltage «U<»
-
Yes
Phase break
No
Yes
"Stiking" phases
No
Yes
Violation of the order of alternation
Yes
Yes
"-"  - on the state of appropriate indicator error has no effect
 Detecting the neutral break in the net is carried out by evaluating phase asymmetry. For symmetrical loading of the three phases the neutral break can not be detected, as soon as the neutral star point under asymmetric load three-phase net will shift, will change the phase voltage inputs on the relay, the neutral break will be detected.
 
CIRCUIT CONNECTION
Схема подключения РКН-3-15-15
 
DIMENSIONS OF THE RELAY
Габаритные размеры реле в корпусе 18*93*62мм
 
Title
Order code
File to download
(manual)
File date
RKN-3-15-15 AC230V/AC400V UHL4
4640016933945
v10.08.16
RKN-3-15-15 AC230V/AC400V UHL2
4640016933952
 
English
You are reporting a typo in the following text:
Simply click the "Send typo report" button to complete the report. You can also include a comment.