Time relay cyclic RVC-R-15 continuously adjustable setting time

Реле времени циклическое РВЦ-Р-15          Реле времени циклическое РВЦ-Р-15
RVC-R-15 АС230V UHL4
по запросу

RVC-R-15 АС230V UHL2
по запросу

RVC-R-15 DC24V UHL4
по запросу

RVC-R-15 DC12V UHL4
по запросу

RVC-R-15 DC6V UHL4
по запросу

 
  • Cyclic relay time with separate adjustment of pulse and pause times
  • The range of setting pause and pulse from 1s to 10h
  • Setting time delay by using two turning decade switches
  • 4 operation diagrams
  • 2 switching groups of contacts
  • The status indicator built-in relay, indicator of availability of power 8A/250V
  • Width of the case 18mm
 
PURPOSE OF THE RELAY
 Time relay RVC-R-15 is designed for switching electric circuits in a cyclic mode with preset time delay (pause and pulse).
        
DESIGN OF THE RELAY
 Relay is produced in a plastic case with a unified front connection wires power and switched circuits. Mounting is carried out on a DIN rail  width 35mm (GOST R IEC 60715-2003) or on a smooth surface. To set on a smooth surface, you need to push locks. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel there are: potentiometer adjustable set time delay pause "PAUSE" (range of values 1-10), potentiometer adjustable set time delay pulse "PULSE" (range of values 1-10), discrete rotary switch to "miltiply" to pause, discrete rotary switch to "multiply" to pulse, green indicator turn on the power supply "U", yellow indicator actuation built-in executive relay «».
 
OPERATION OF THE RELAY
 The relay has 5 sub-bands delay pause time and 5 sub-bands delay pulse time. The required delay pause (tpause) is determined by multiplying the numerical value set on the scale of the potentiometer "Pause" on multiplier the selected range on the switch "multiply" pause. The required delay pulse (tpulse) is determined by multiplying the numerical value set on the scale of the potentiometer "Pulse" on multiplier the selected range on the switch "multiply" pulse.
  Operation diagram is determined by two switches "multiply" pause and "multiply" pulse. Each of the switches has two installation zones. At switch "multiply" pause there are "A" and "B" zones, at switch "multiply" pulse there are "C" and "D" zones. Depending on the combination of installed switch selects one of the four positions of the relay diagrams.
 A switch "multiply" pause in zone "A", a switch "multiply" pulse in zone "C" - diagram 7.
 A switch "multiply" pause in zone "B", a switch "multiply" pulse in zone "C" - diagram 8.
 A switch "multiply" pause in zone "A", a switch "multiply" pulse in zone "D" - diagram 9.
 A switch "multiply" pause in zone "B", a switch "multiply" pulse in zone "D" - diagram 10.
 
 WARNING:  Changing the operation diagrams and multipliers is possible only after removal of the voltage.
 In the currentless position the contacts 15-16 are closed. After the supplying voltage lights up green LED «U», relay begins to work the selected diagram, during the reference set time the green «U» indicator light flashes with a period of 0,5s.
 When the executive relay is turned on the yellow indicator «» lights up and contacts 15-18 and 25-28 closes.
 
SPECIFICATION OF THE RELAY RVC-R-15
A parameter Unit RVC-R-15
Supply voltage
V
АС230
DC24
DC12
DC6
Range of the delays time pulse and pause
 
1-10s; 0,1-1min; 1-10min; 0,1-1h; 1-10h
Deviation of installation time delay, not more
%
10
Deviation of counting time delay, not more
%
2
Repeated availability time, not more
s
0,1
Exposure time control signal, not less
s
0,05
Operating diagrams
 
7, 8, 9 и 10
Maximum switching current: AC250V 50Hz (AC1)/DC30V (DC1)
A
8
Maximum switching voltage V 400 (AC1/2A)
Maximum switching power: АС250V 50Hz (АС1)/DC30V (DC1)
VA/W
2000/240
The maximum voltage between the power supply circuits and relay contacts
V
АС2000 (50Hz - 1min)
Power consumption, max
VA 2
Mechanical endurance, not less
cycles
10х106
Electrical endurance, not less
cycles
100000
Quantity and type of contacts   2 switching group
Operating temperature range (different versions)
0C
-25…+55 (UHL4)
-40…+55 (UHL2)
Storage temperature
0С
-40 ... +70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)   level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)   level 3 (2kV A1-A2)
Climatic modification and placement category by GOST 15150-69 (non-condensing)
  УХЛ4 или УХЛ2
The degree's protection at case/terminals according to by GOST 14254-96
  IP40/IP20
The degree of pollution in accordance with GOST 9920-89
  2
Relative humidity of air
%
up to 80 (at 250C)
Height above sea level
m
till 2000 
Operating position in space
 
artbitrary
Mode
 
round the clock
Dimensions
mm
18х93х62
Weight
kg
0,062
 
DIAGRAMS OF OPERATING THE RELAY
Диаграмма работы реле времени № 7
 Cyclical switching on and off the relay (infinite loop). When the supply voltage begins count delay time tpause, after working time, pauses, the output relay is turned on and begins count time delay tpulse, after working the output relay pulse time off. The cycle is repeated before removal of voltage.
Диаграмма работы реле времени № 8
 Cyclical switching on and off the relay (infinite loop). When the supply voltage, the output relay is turned on and begins count time delay tpulse, after working out the pulse of time, the output relay is turned off and start count time delay tpause. The cycle is repeated before removal of voltage.
Диаграмма работы реле времени № 9
 Cyclic relay with a single cycle. When the control contact starts count time delay tpause, after working time, pauses, the output relay is turned on and begins to count delay time tpulse, the output relay switches off after working pulse.
Диаграмма работы реле времени № 10
 Cyclic relay with a single cycle. When the supply voltage, the output relay is turned on, count time delay tpulse is started after control contact closure, after working the output relay pulse time off and start count time delay tpause, after working time, pauses, the output relay is turned on.
 
CIRCUIT CONNECTION
Схема подключения РВЦ-Р-15
  Voltage supply AC230V is fed to the terminals "A1" and "A2", ACDC24V to terminals "+ A3" and "A2". Command of external control is supplied to the "Y1" terminal and is formed by closing a dry contact «S» between terminal "Y1" and terminal "A1" or "+ A3".
 
DIMENSIONS OF THE RELAY
Габаритные размеры реле контроля фаз ЕЛ-11М-15
 
Title
Order code
File to download
(manual)
File date
RVC-R-15 АС230V UHL4
4640016933723
25.02.2016
RVC-R-15 АС230V UHL2
4640016933716
RVC-R-15 DC24V UHL4
4640016936311
RVC-R-15 DC12V UHL4
4640016933730
RVC-R-15 DC6V UHL4
4640016936304
 
English
You are reporting a typo in the following text:
Simply click the "Send typo report" button to complete the report. You can also include a comment.