Phase selection relay RVF-01, RVF-02, single phase AVR with 16A contact group

 Реле выбора фаз РВФ-02
RVF-01 AC230V UHL4
2600.00 руб. с НДС

RVF-01 AC230V UHL2
2860.00 руб. с НДС

RVF-02 AC230V UHL4
2950.00 руб. с НДС

RVF-02 AC230V UHL2
4071.00 руб. с НДС

 
  • Up to 3 inputs voltage sources (3 phases) AC230V 45-65Hz with a common zero
  • Switchable restart delay - 1s, 5s, 30s, 2min, 10min
  • Operate with the priority phase L1 or without priority
  • Indication of the phase voltages at the input and output phase enabled
  • Two-threshold overvoltage protection >АС265V/0,1s and >AC300V/0,02s
  • Two-threshold undervoltage protection <AC157-209V/10s (smooth adjustment of the threshold) and <AC130V/0,1s (fixed threshold)
  • Protection against interphase circuits when switching due to the control operation of built-in relays or external contactors
  • Constant control of serviceability of starters (only for RVF-02)
 
PURPOSE OF THE RELAY
 The phase selection relay RVF-01, RVF-02 (phase commutator, phase switch) a single-phase unit of automatic transfer switch (further - AVR) is connected, tupically, to three phase main and provides for switching single-phase consumers at power phase optimal at level of voltage at oscillations or a complete failures of the supply voltage "operating" phase. AVR provides constant monitoring of the quality and availability and quality of voltage on the phases, in dependence on parameters, automatically selects the most optimal phase and high speed switches a power to the single-phase load to this phase. When switching from phase to phase, to exclude interphase closures, AVR checks off the alarm phase, and only afterwards includes reserve.
 In the case of sticking of contacts relay or contactor, AVR does not switch to a different phase, even at the output of a voltage in this phase of the set limits (from circuit protection between phases).
 RVF-01 - without function of control state external contactors (winding break, contacts burning, etc)
 RVF-02 - with function of control state external contactors (winding break, contacts burning and etc)
 AVR can operate with 2 or 3 independent sources of single-phase voltage, frequency from 45 to 65Hz. Can be used in a single-phase net, and as an additional phase - electrogenerator.
 It is used in nets with unstable voltage for supply security and fire alarm systems, video surveillance, unauthorized access, industrial and technological, and other single-phase equipment with a continuous cycle operation.
 There is the option to return to the priority phase after switching to reserve, i.e. return power of the load from the priority phase after recovery a voltage.
 
DESIGN OF THE RELAY
 Relay is produced in a unified plastic case with front connection wires power and switched circuits. Mounting is carried out on a DIN rail  width 35mm (GOST R IEC 60715-2003) or on a smooth surface. To set on a smooth surface, spring locks must be changed in recent holes, fixing a spring lock, which are located on the back side of the case. Terminal design provides robust clamp wires up to 2,5mm2. On the front panel there are: 3 green indicators of availability voltage of phase "A1", "A2" and "A3", 3 yellow indicators of actuation built-in executive relay "B1", "B2" and "B3", regulator of turning on relay "ton",  regulator of return time "treturn", regulator of threshold actuation undervoltage "Umin".
 
OPERATION OF THE RELAY
 AVR has three independent inputs, terminals "A1" (priority phase) and "A2", "A3" (reserve phase) and output terminals "B1", "B2", "B3" accordingly to connect the load. Terminal «N» to connect the neutral wire, terminal «Y1» designed for controlling the state of switching relay contacts or additional contactors required to increase the load capacity. AVR allows to connect load up to 16A (3,5kW) directly to the device. When power exceeding 3,5kW (16A) AVR controls single-phase coils of magnetic contactors of appropriate power.
 When powering AVR checks the voltage on the priority phase, and if all the parameters are within acceptable values, connects the load through a predetermined by user delay on the enabling. If the value of the priority phase voltage does not comply with parameters, AVR checks the reserve phase and connects the load through it. When restoring the power supply voltage on the priority phase, AVR switches to it load, through a user-defined return time.
 
Recommendations:
 If AVR switches a large load capacity, it is recommended to include priority mode, which allows, after recovering the mains parameters, return to the priority phase. This avoids overloading reserve phase.
 In all other cases, the priority function is not required.
 In the absence of the circuit contactors, terminal «Y1» not necessary to use (only for the relay RVF-01).
  When connecting external contactors must be selected relay RVF-02 and use «Y1» terminal to monitor the state of switching devices.
 It is recommended to use the delay of actuation time during short voltage dips.
 
SPECIFICATION OF THE RELAY RVF-01, RVF-02
A parameter Unit RVF-01, RVF-02
Urated/frequency
V/Hz
230/45-65
Umax
V
400
Adjustable switching threshold (off) at undervoltage Ulow; reaction time 10s
V
154-209
Hysteresis of a voltage
V
5-7
The accuracy of determining threshold of actuation
V
±3
Switching threshold (off) at overvoltages; reaction time 0,1s
V
>265
Rapid switching threshold (off) at overvoltages; reaction time 20ms
V
>300
Rapid switching threshold (off) at undervoltages; reaction time 0,1ms
V
<130
ton repeated
s
1s, 5s, 30s, 2min,10min
treturn to the priority phase
s
from 5 to 150
Ability to disable the priority phase
 
there is
Switching time on reserve phase, not more
s
0,1
Switching current output contacts, not less
A
16
Power consumption (under load), max
VA
1,0
Resource output contacts under load 16A, cycles not less
pcs
1х106
The degree's protection at case/terminals according to by GOST 14254-96
 
IР40/IР20
Climatic modification and placement category by GOST 15150-69 (non-condensing)
  UHL4 or UHL2
Operating temperature range (different versions)
оС
-25…+55 (UHL4)
 -40…+55 (UHL2)
Storage temperature
оС
-45…+70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)   level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)   level 3 (2kV A1-A2)
The degree of pollution in accordance with GOST 9920-89
  2
Relative humidity of air   up to 80 (at 250C)
Height above sea level m till 2000
Operating position in space
 
artbitrary
Mode   round the clock
Dimensions
mm
18х93х62
Weight
kg
0,2
 
DIAGRAMS OF OPERATING THE RELAY
Диаграмма работы РВФ-01, РВФ-02
 
CIRCUIT CONNECTION
Direct control of load (Iload<16A)
Control of load through magnetic starters (Iload<16A)
Схема подключения РВФ-01, РВФ-02
Схема подключения РВФ-01, РВФ-02 (2)
 
DIMENSIONS OF THE RELAY
Габаритные размеры реле в корпусе 18*93*62мм
 
Title
Order code
File to download
(manual)
File date
RVF-01 АС230V UHL4
4640016932535
07.06.2015
RVF-01 АС230V UHL2
4640016932528
RVF-02 АС230V UHL4
4640016932559
RVF-02 АС230V UHL2
4640016932542

 

English