3-phase over/under voltage protection device UZM-3-63 (multifunction protection device), load 63A

UZM-3-63K AC230V/AC400V UHL4
3800.00 руб. с НДС

UZM-3-63K AC230V/AC400V UHL2
5244.00 руб. с НДС

 
  • Have the terminal for remote control
  • Three-phase two-threshold overvoltage protector (trip delay): >265V/0,2s; >300V/20ms
  • Three-phase two-threshold undervoltage protector (trip delay): <170V/10s; <1340V/100ms
  • Monitoring phase failure and phase sequence
  • The maximum switching current of 63A per phase (14,5kW at 3)
  • Decade switch of thresholds
  • Reclosure delay (0,1 to 10 seconds) (continuous adjustment)
  • Frequency control from 45 to 55 Hz
  • Built-in varistor protection from impulse perturbation network
  • Switchable delay reclosing from 2s to 8 minutes
  • Operate time when the voltage jumps - less than 30ms
 
PURPOSE OF THE DEVICE
 Protection device UZM-3-63K is a kind of three-phase voltage monitoring relay with built-in powerful three-phase polarized relay, allowing to switch high currents. The device contains control function of the mains frequency. This allows you to use it to turn on/off the load when operating on an autonomous generator, as well as to protect the various electrical equipment from the mains voltage alarm. The device provides protection equipment (industrial, administrative and housing purpose) from the damaging effects of pulsed power surges caused by the actuation of closely spaced and connected to the same network of electric motors, magnetic starters or electrical surges on the TS (transformer substations), preventing equipment damage. Varistor protection for each phase ensures that the operability when subjected to surges duration of 8/20mks amplitude of up to 6500A.
 The device does not replace other protection devices (circuit breakers, surge arresters, RCDs, etc..). When short-term loss of mains voltage below the set value, load disconnection occurs, it does not disable the user and re-inclusion of a set delay time.
 
DESIGN OF THE DEVICE
  The device is mounted on a DIN rail-DIN 35 mm (GOST R IEC 60715-2003) with a front connecting wires power switched circuits. Terminals of device provide connectivity wires up to 35mm2. Recommended conductor cross-section are shown in the table below. On the front panel there are: rotary switch "Umax" (maximum voltage), rotary switch "Umin" (minimum voltage), rotary switch reclosing time, the red LED «U>» excess of line voltage, yellow LED "" connect the load to the consumer, the red LED «U<» reduction of the line voltage below the set value, the three green LED «L1», «L2», «L3» presence of linear phase voltages.
 Terminals for input buses are marked N, L1, L2, L3 and the inscription ENTER. load connection terminals are marked N, U, V, W and inscription EXIT. The terminals for connecting the remote control are marked Y1 and Y2.
 
OPERATION OF THE DEVICE
  Connect the equipment according to the circuits connection. Verify that contact  of the terminal remote terminal is in closed state, otherwise the device will not connect the load indicators, in this indicators «> U», «<U» and «» will alternately switch.
  After voltage supply to the input power supply, included green LEDs «L1», «L2», «L3». If input voltage is within the specified value and the correct phase sequence, connected load is switched on and the yellow LED "". If the voltage is below the set value the red LED «U<» and load shedding occurs, the yellow LED "" disabled. After restoring the voltage at the input, connect the load and the inclusion of yellow indicator "" occurs after the reference time delay set by the user. Operation at the value of the input voltage is higher than the value of the same. The device monitors the phase sequence, the reduction or excess mains frequency and voltage difference in the phases of greater than 25%.
 
Operation of indicators «>U», «<U», depending alarm situation:
  • Breach of phase sequence - alternate inclusion indicators.
  • Increase or decrease in power frequency more than 55 Hz, 45 Hz or less - often simultaneously inclusion indicators.
  • When a voltage difference of more than 25% between any phases - slow simultaneous inclusion indicators.
 
 When the network of high voltage pulses on the input protection varistor shunts pulses in any phase at the neutral conductor N, excluding the passage of the pulse to the load. The diagram device operation is shown below.
 
WARNING: At operation of the device breaks all - phase bus. Zero wire (N) passes on through for ease of installation and not switches. Connect the neutral wire to terminal N is must!
 
Table recommended cross section that can be connected
Curent, A
8
10
13
16
20
25
32
40
50
63
kW
230V
1,8
2,3
3,0
3,7
4,6
5,8
7,4
9,2
11,5
14,5
mm2
copper
1,0
1,0
1,0
2,0
2,5
4,0
6,0
10,0
10,0
16,0
 
aluminium
2,5
2,5
2,5
2,5
4,0
6,0
10,0
16,0
16,0
25,0
 
SPECIFICATION OF THE UZM-3-63K
A parameter Unit UZM-3-63K
Protection parameter
The threshold of load disconnection at increasing voltage, Umax (toff=0,5s) V 243, 249, 255, 261, 267, 273, 279, 285, 291, 297±3
The threshold of load disconnection at decreasing voltage, Umin (toff=10s) V 217, 211, 205, 199, 193, 187, 181, 175, 169, 163±3
The threshold of accelerated load disconnection at a jump voltage (toff=30ms) V 300
The threshold of off load at voltage failure (toff=100ms) V 110
Tolerance voltages in phases, not more 25
Frequency of threshold Hz 45/55 ±0,5
The level of voltage limit at interference current 100A, not more
kV
1,2
The maximum absorption energy (single pulse of 10/1000 microseconds)
J.
200
The maximum absorption current single pulse 8/20/pulses 8/20 microseconds
A
6500/4500
Actuction time of protection from pulse action
ns
<25
Power supply
Rated supply voltage
V
230
Frequency of supply voltage
Hz
50
Maximum supply voltage
V
440
Сonsumption of electricity
VA
2,2
Switching capacity of contacts
Rated load current(at the section of connected conductors not less than 16mm², copper)
A
63/AC250V
Rated power of load (AC250V) in every phase
kW
14,5
Maximum switching voltage
V
400
The maximum allowable short-circuit current (not more 10ms)
A
4500
Technical data
Delay on/reclosing, user selectable
 
2s, 5s, 10s, 15s, 20s, 30s, 1min, 2min, 4min, 8min
The delay off when the voltage is above the upper threshold
s
0,2
The time of acclelerated load off  at jump of a voltage, toff ms 30
The delay off when the voltage is below the lower threshold
s
10
The time of load off at below voltage, toff ms 100
Cross-sectional wiring of not less than
mm²
0,5-25 (20-4 AWG)
Operating temperature range (different versions)
0С
-25…+55 (UHL4)
-40…+55 (UHL2)
Storage temperature 0С –40...+70
Immunity to interference from bursts in accordance with GOST R 51317.4.4-99 (IEC/EN 61000-4-4)   level 3 (2kV/5kHz)
Immunity to interference over voltage in accordance with GOST R 51317.4.5-99 (IEC/EN 61000-4-5)   level 3 (2kV А1-А2)
Climatic modification and placement category by GOST 15150-69 (non-condensing)   UHL4 и UHL2
The degree's protection at case/terminals according to by GOST 14254-96   IP40/IP20
The degree of pollution in accordance with GOST 9920-89   2
Relative humidity of air % up to 80 (at 25°С)
Height above sea level м till 2000
Operating position in space   artbitrary
Mode   round the clock
Dimensions mm 105х63х94
Weight, not more kg 0,45
Service life, not less than
years
10
 
DIAGRAM OF WORK DEVICE
Диаграмма работы УЗМ-3-63
Диаграмма работы УЗМ-3-63 (1)
 
CIRCUITS CONNECTION OF DEVICE
   Схема подключения УЗМ-3-63К
 
DIMENSIONS OF THE DEVICE
Габариты УЗМ-3-63
 